HOME|RESIDENTS|BUSINESS|VISITORS|GOVERNMENT|FORMS|FAQs|CONTACT US
Home > Residents > Inspection Services > Fire Alarm System Submittal Requirements

Community Planning and Development Services Department
Inspection Services Division

Fire Alarm System Submittal Requirements

Permit Procedures

General Submittal Requirements

Drawings

Equipment

Wiring Diagram

Riser Diagram

Show all devices and panels.  Give all wire counts.

Sequence of Operations

For all initiating devices, show all system outputs such as audible and visual devices, annunciation, door and damper closure, AHU shutdown, door unlocking, smoke control system activation, sprinkler system activation, etc.  This must be in matrix form for high-rises.

Battery Calculations

Show all devices and current draw.  Provide the required alarm and supervision time.

Circuit Calculations

Show all devices and current draw.  Show total circuit load, not to exceed maximum circuit capacity.